型號 Model | GF-7A (25kA) | GF-12A (40kA) |
額定電壓 Rated voltage | 69 kV ( 72.5 kV ) | |
額定電流 Rated current | BUS:2000 A ; CB:2000 A | BUS:2000/3150 A ; CB:2000 A |
額定頻率 Rated frequency | 60 Hz | |
額定啟斷容量 Rated breaking capacity | 25kA | 40 kA |
額定短時間電流 Rated short time current | 25 kA 3 sec | 40 kA 3 sec |
額定啟斷時間 Rated breaking time | 5 cycles | |
低頻耐壓 Low frequency withstand | 160 kV | |
衝擊耐壓 Impulse withstand | 350 kV | |
標準操作責務 Standard operation duty | O - 0.3s - CO - 15s - CO | |
GIS 額定氣體壓力 Rated gas pressure of GIS | CB:5.0 kgf/cm² ( at 20℃ ) OTHER:5.0 kgf/cm² ( at 20℃ ) |
CB:0.65Mpa ( at 20℃ ) OTHER:0.45Mpa、0.5Mpa ( at 20℃ ) |
操作方式 Operation | 電動或手動儲能 / 彈簧作動 Electric or Manual / spring charging |
|
依據規範 Based on standards | IEC 62271-203 | |
安裝場所 Installed location | 屋內 / 屋外 Indoor / Outdoorion |